Target differential pressure across the chilled water loop, used to control chilled water pump speed. Ensures adequate flow to all coils.

Brick

Chilled_Water_Differential_Pressure_Setpoint

Category

setpoints

Typical Range

-

Object Type

-

Haystack

Tags

chilledMarkerwaterMarkerdifferentialMarkerpressureMarkerspMarkerpointMarker

Kind

Number

Point Function

setpoint

Haystack Unit

psi

Source Units

PSI / ft H₂O / kPa

States

-

Aliases

Common

Common Misspellings

chilled-water-diferential-pressure-sp

Notes

  • Controls variable speed pump operation to maintain adequate pressure across the most remote coil
  • ASHRAE Guideline 36 recommends differential pressure reset based on valve positions
  • Sensor should be located at the most hydraulically remote coil, not at the pump discharge
  • Typical range is 5-25 PSI depending on system size