BAS ATLAS
Back to BAS Atlas
point
Chilled Water Supply Temperature
Temperature of chilled water leaving the chiller plant
Brick
Chilled_Water_Supply_Temperature_Sensor
Category
temperatures
Typical Range
-
Object Type
-
Haystack
Tags
chilledMarkerwaterMarkerleavingMarkertempMarkersensorMarkerpointMarker
Kind
Number
Point Function
sensor
Haystack Unit
°F
Source Units
°F / °C
States
-
Aliases
Common
Common Misspellings
-
Notes
- Typical setpoint 42-44°F for comfort cooling
- Higher setpoints (50-55°F) for energy optimization
- Must stay above 40°F to prevent coil freezing
- Delta T from return typically 10-14°F