Communication Loss Alarm

Alarm indicating loss of communication between a BAS controller and a supervised device or sensor. May indicate network failure, device failure, or wiring issue.

Brick

Communication_Loss_Alarm

Category

maintenance

Typical Range

-

Object Type

-

Haystack

Tags

commMarkeralarmMarkerpointMarker

Kind

Bool

Point Function

alarm

Haystack Unit

-

States

0normal, communicating, online
1comm-loss, offline, no-response, communication-failure

Aliases

Common

Common Misspellings

comunication-loss

Notes

  • One of the most common alarms in any BAS
  • May be caused by wiring issues, power loss at the device, or network switch failure
  • Should trigger investigation within hours to prevent uncontrolled equipment operation