Skip to main content
BAS ATLAS
Back to BAS Atlas
point

Condenser Water Supply Temperature Setpoint

Target condenser water temperature leaving the cooling tower and entering the chiller condenser. Controls cooling tower fan speed.

Brick

Condenser_Water_Supply_Temperature_Setpoint

Category

setpoints

Typical Range

-

Object Type

-

Haystack

Tags

condenserMarkerwaterMarkerleavingMarkertempMarkerspMarkerpointMarker

Kind

Number

Point Function

setpoint

Haystack Unit

°F

Source Units

°F / °C

States

-

Aliases

Common

Common Misspellings

condensor-water-sp

Notes

  • Typical range is 70-85°F (21-29°C) depending on weather and chiller requirements
  • Lower condenser water temperature improves chiller efficiency but increases tower fan energy
  • Optimal setpoint balances chiller and tower energy (often calculated via chiller COP curves)
  • Minimum is limited by chiller manufacturer low-condenser-water cutout (typically 55-65°F)