Skip to main content
BAS ATLAS
Back to BAS Atlas
point

Daylight Illuminance

Measured natural daylight intensity at a sensor location, in lux. Used for daylight harvesting to reduce electric lighting usage.

Brick

Illuminance_Sensor

Category

lighting

Typical Range

-

Object Type

-

Haystack

Tags

lightMarkerilluminanceMarkersensorMarkerpointMarker

Kind

Number

Point Function

sensor

Haystack Unit

lux

Source Units

lux / fc

States

-

Aliases

Common

Common Misspellings

daylite-sensorilluminence

Notes

  • Typical office target is 300-500 lux (30-50 fc) at the task plane
  • Sensor placement impacts accuracy — avoid direct sunlight on the sensor
  • Used to modulate electric lighting in daylight harvesting sequences