Fire Alarm Status
Fire alarm system general alarm status. When active, BAS systems typically execute smoke control sequences including fan shutdown, damper closure, and elevator recall.
Brick
Fire_Alarm_Status
Category
alarms
Typical Range
-
Object Type
-
Haystack
Tags
fireMarkeralarmMarkerpointMarker
Kind
Bool
Point Function
alarm
Haystack Unit
-
States
0normal, no-alarm, clear
1fire-alarm, alarm-active, fire-detected
Aliases
Common
Common Misspellings
fier-alarm
Notes
- This is a monitoring point from the fire alarm panel — the BAS does NOT control fire alarm systems
- Triggers smoke control sequences defined by the fire protection engineer
- Typically a dry contact input from the fire alarm control panel (FACP)
- All smoke dampers close and fans shut down (or enter smoke evacuation mode) on fire alarm