BAS ATLAS
Back to BAS Atlas
point
Hot Water Supply Temperature Setpoint
Target supply temperature for hot water leaving the boiler or hot water plant. Controls boiler firing and hot water system operation.
Brick
Hot_Water_Supply_Temperature_Setpoint
Category
setpoints
Typical Range
-
Object Type
-
Haystack
Tags
hotMarkerwaterMarkerleavingMarkertempMarkerspMarkerpointMarker
Kind
Number
Point Function
setpoint
Haystack Unit
°F
Source Units
°F / °C
States
-
Aliases
Common
Common Misspellings
hot-water-suply-temp-sp
Notes
- Typical range is 140-180°F (60-82°C)
- Lower setpoints reduce boiler losses and improve condensing boiler efficiency
- Often reset based on outdoor air temperature (outdoor air reset schedule)