BAS Point-to-Point Checkout Procedures
Point-to-point (P2P) checkout is a systematic verification process that confirms every input and output in a building automation system is correctly wired, addressed, and functioning. This critical commissioning step catches wiring errors before they cause operational problems.
What is Point-to-Point Checkout?
Point-to-point verification confirms that:
- Physical sensors/actuators are wired to correct controller terminals
- Controller I/O addressing matches design documents
- Signal types match (voltage, current, resistance)
- Measured values are reasonable and accurate
- Actuators respond correctly to commands
Why P2P is Essential
- Catches wiring errors early: Easier to fix during construction
- Validates documentation: Confirms as-builts match reality
- Prevents equipment damage: Wrong signals can damage sensors or actuators
- Establishes baseline: Documents initial calibration state
- Required by specs: Most commissioning specs mandate P2P
Preparation
Documentation Required
- Control drawings: I/O schedules, wiring diagrams
- Submittal data: Sensor ranges, actuator specifications
- Points list: Complete BAS points with addresses
- Sequence of operations: Expected behavior reference
- P2P forms: Standardized checkout sheets
Tools Needed
- Digital multimeter (DMM)
- Temperature reference (ice bath, calibrated thermometer)
- Pressure reference (manometer, calibrated gauge)
- Current source/simulator (4-20mA)
- Laptop with BAS software access
- Two-way radios for coordination
Pre-Checkout Verification
Before starting P2P:
Input Point Verification
Temperature Sensors (Thermistors/RTDs)
Procedure:
- Identify sensor location and type from drawings
- Access BAS point value on workstation
- Compare displayed value to reference thermometer at sensor
- Document deviation
Acceptance Criteria (typical):
- Space temperature: ±1°F (±0.5°C)
- Duct temperature: ±1°F (±0.5°C)
- Water temperature: ±1°F (±0.5°C)
- Outside air temperature: ±2°F (±1°C)
Common Issues:
- Wrong thermistor type selected in software
- Sensor in poor location (direct sunlight, near heat source)
- Wiring reversed (if using RTDs)
Pressure Sensors
Procedure:
- Verify sensor range matches application
- Zero sensor at atmospheric pressure (if applicable)
- Apply known pressure using manometer
- Compare BAS reading to reference
Acceptance Criteria:
- ±2% of full scale (typical)
- Zero offset: ±0.05" w.c. for duct pressure
Common Issues:
- Tubing connected to wrong port (high/low reversed)
- Units mismatch (inches w.c. vs. Pa)
- Calibration offset not set
Current Inputs (4-20mA)
Procedure:
- Disconnect sensor
- Connect current source to input terminals
- Apply 4mA, verify 0% reading
- Apply 12mA, verify 50% reading
- Apply 20mA, verify 100% reading
- Reconnect sensor and verify live reading
Acceptance Criteria:
- ±1% of span at each test point
Binary/Digital Inputs
Procedure:
- Identify normal state (NO/NC)
- Actuate switch/contact manually
- Verify BAS state change matches physical state
- Verify alarm generation if applicable
Common Issues:
- NO/NC configured backwards
- Supervision resistors not installed
- Contact bounce causing false triggers
Output Point Verification
Analog Outputs (AO)
Procedure:
- Command output to 0%
- Measure voltage or current at terminals
- Command to 50%, measure again
- Command to 100%, measure again
- Verify actuator responds proportionally
Acceptance Criteria:
- 0-10V outputs: ±0.2V at each point
- 4-20mA outputs: ±0.4mA at each point
Actuator Stroke Verification:
- Command 0%: Actuator fully closed/minimum
- Command 50%: Actuator at midpoint
- Command 100%: Actuator fully open/maximum
- Verify stroke direction matches sequence
Binary/Digital Outputs (DO)
Procedure:
- Command output ON
- Verify relay energizes (listen for click or measure coil)
- Verify controlled device operates
- Command output OFF
- Verify relay de-energizes and device stops
Safety Verification:
- Test with equipment safeties active
- Verify interlock operation
- Document hand-off-auto switch positions
Documentation
P2P Checkout Form Contents
Each point should document:
- Point name and address
- Design value/range
- Measured/commanded value
- Reference instrument used
- Pass/fail status
- Technician initials and date
- Notes on corrections made
Sample Form Structure
| Point ID | Description | Design Range | Measured | Reference | Pass/Fail | Notes |
|----------|-------------|--------------|----------|-----------|-----------|-------|
| AHU1-SAT | Supply Air Temp | 55-85°F | 72.3°F | Fluke 54II | Pass | Cal OK |
| AHU1-SF-CMD | Supply Fan Start | On/Off | On | Visual | Pass | - |
Issue Tracking
Document all issues found:
- Point identification
- Issue description
- Root cause
- Corrective action taken
- Retest result
Common Issues and Solutions
Wiring Problems
| Symptom | Likely Cause | Solution |
|---|
| Reading stuck at min/max | Open wire or short | Check continuity, repair |
| Erratic readings | Loose termination | Re-terminate, torque to spec |
| Wrong polarity | Wires reversed | Swap at terminals |
| Interference/noise | Poor shielding | Verify shield grounding |
Configuration Problems
| Symptom | Likely Cause | Solution |
|---|
| Wrong units displayed | Scaling incorrect | Adjust I/O configuration |
| Value offset | Calibration needed | Apply offset in software |
| Wrong point addressed | Database error | Correct address mapping |
| Inverted operation | NO/NC or direction wrong | Change configuration |
Best Practices
Efficiency Tips
- Work systematically: Go panel by panel, not random
- Two-person team: One at field device, one at workstation
- Use radios: Clear communication prevents errors
- Pre-fill forms: Enter design data before field work
- Fix issues immediately: Don't defer "minor" problems
Quality Assurance
- Independent verification of critical points
- Supervisor spot-checks of completed P2P
- Complete documentation before system turnover
- Archive all P2P records with O&M manuals
References
- ASHRAE Guideline 1.1: HVAC&R Technical Requirements for the Commissioning Process
- NEBB Procedural Standards for Building Systems Commissioning
- AABC Commissioning Guideline
Point-to-point checkout is tedious but essential. Time invested during P2P prevents countless hours of troubleshooting later.