Proper boiler staging balances heating capacity with demand while optimizing efficiency. This guide covers sequencing strategies for multiple boiler systems.
| Boiler Type | Peak Efficiency | Best Loading |
|---|---|---|
| Non-condensing | 80-85% | 50-100% |
| Condensing | 90-98% | 20-50% |
| Modulating | Higher part-load | Variable |
Key insight: Condensing boilers are most efficient at part load with low return water temperatures.
Rotate lead boiler to equalize runtime:
| Method | Description |
|---|---|
| Weekly rotation | Auto-switch every Sunday |
| Runtime-based | Rotate when lag equals lead hours |
| Seasonal | Rotate at season start |
| Manual | Operator-initiated |
Stage Up: If HWS_Temp < Setpoint - 5°F for > 15 minutes: Stage on next boiler
Stage Down: If HWS_Temp > Setpoint + 5°F for > 15 minutes AND Lead boiler < 30% fire: Stage off lag boiler
Setpoint = Reset_Schedule(OAT)
Stage Up: If HWR_Temp < (Setpoint - Deadband) AND Lead boiler > 80% fire: Stage on next boiler
Stage Down: If HWR_Temp > (Setpoint + Deadband) AND Total fire rate < 40%: Stage off lag boiler
Load = GPM × ΔT × 500 / 1000 (MBH)
Stage Up: If Load > (Online_Capacity × 85%): Stage on next boiler
Stage Down: If Load < (Online_Capacity × 40%) AND (N-1) boilers can meet load: Stage off lag boiler
Adjust hot water setpoint based on outdoor temperature:
| OAT | HWS Setpoint |
|---|---|
| 70°F | Off (or 90°F standby) |
| 50°F | 120°F |
| 30°F | 160°F |
| 0°F | 180°F |
Linear formula: HWS_SP = 180 - (OAT - 0) × (180-120)/(50-0) = 180 - (OAT × 1.2) [simplified]
| Benefit | Description |
|---|---|
| Energy savings | Lower temps = lower losses |
| Condensing operation | Return < 130°F enables condensing |
| Longer cycles | Less short-cycling |
| Comfort | Better match to actual load |
Condensing boilers require return water < 130°F to condense:
Strategies:
For plants with all condensing boilers:
Traditional: Run few boilers at high fire Condensing: Run more boilers at low fire
Stage Up: May improve efficiency by distributing load Stage Down: May hurt efficiency by concentrating load
Before enabling boiler:
| Condition | Action |
|---|---|
| High limit | Trip boiler |
| Low water | Trip boiler |
| Flame failure | Lockout until reset |
| High stack temp | Reduce fire, alarm |
| Parameter | Typical Value |
|---|---|
| Minimum ON time | 10-15 minutes |
| Minimum OFF time | 5-10 minutes |
| Stage delay | 5-10 minutes between stages |
| Post-purge | Per manufacturer |
| Point | Purpose |
|---|---|
| HWS temperature | Control verification |
| HWR temperature | Efficiency indicator |
| Stack temperature | Combustion efficiency |
| Gas consumption | Energy tracking |
| Runtime hours | Maintenance planning |
| Alarm | Setpoint |
|---|---|
| Low HWS temp | Setpoint - 10°F |
| High HWS temp | 200°F or limit |
| Boiler lockout | Any safety trip |
| Short cycling | >6 cycles/hour |
Causes:
Solutions:
Symptoms: One boiler works hard, others idle
Causes:
Solutions:
Symptoms: High gas use, low return temps not achieved
Causes:
Solutions: