Distech and Trend 4-20mA Sensor Setup on APEX UIO
This guide covers configuring 4-20mA analog inputs on Distech APEX UIO controllers, specifically addressing common issues with Trend T/PI sensors.
Understanding 4-20mA Configuration
4-20mA current loop sensors require specific configuration:
| Parameter | Typical Setting |
|---|
| Input Type | 4-20mA (Active) |
| Scaling | Linear |
| Low Range | 4mA = minimum engineering value |
| High Range | 20mA = maximum engineering value |
| Units | Engineering units (°F, PSI, etc.) |
APEX UIO Input Configuration
Hardware Setup
Important: 4-20mA inputs on APEX UIO require proper jumper/DIP switch configuration:
- Locate input configuration switches on the UIO module
- Set to current mode (mA) not voltage mode
- Verify loop power - Some sensors are 2-wire (loop-powered), others are 4-wire (externally powered)
Software Configuration in EC-Net
- Navigate to the analog input point
- Set Input Type to "4-20mA" or "Current"
- Configure Scaling:
- Min Raw Value: 4 (representing 4mA)
- Max Raw Value: 20 (representing 20mA)
- Min Engineering Value: (sensor minimum, e.g., 0°F)
- Max Engineering Value: (sensor maximum, e.g., 100°F)
- Set appropriate Engineering Units
Common Issues and Solutions
Issue 1: Reading Shows Zero or Negative
Cause: Input configured for thermistor instead of current
Solution:
- Verify input type is set to 4-20mA, not thermistor
- Check hardware jumper/switch position
Issue 2: Reading is Erratic or Out of Range
Cause: Missing or incorrect loop power
Solution for 2-wire sensors:
- Verify 24VDC loop power is provided
- Check polarity (+ and - correct)
- Measure loop current with meter in series
Solution for 4-wire sensors:
- Verify external power supply to sensor
- Signal wires connect to input terminals only
Issue 3: Value Stuck at Minimum or Maximum
Cause: Open or shorted wiring
Diagnosis:
- Open loop reads ~0mA (value at minimum)
- Shorted loop reads >20mA (value at maximum or error)
Solution:
- Check wiring continuity
- Verify sensor is operating (measure current at sensor)
- Look for damaged conductors
Issue 4: Incorrect Scaling/Offset
Cause: Sensor range doesn't match configuration
Example - Trend T/PI Sensor:
The Trend T/PI (temperature/pressure indicator) may have different ranges depending on model:
| Model | Range | 4mA Value | 20mA Value |
|---|
| T/PI Temp | 0-100°F | 0°F | 100°F |
| T/PI Temp | -20-120°F | -20°F | 120°F |
| T/PI Pressure | 0-150 PSI | 0 PSI | 150 PSI |
Solution:
- Find exact sensor model number
- Verify sensor range from datasheet
- Match scaling in controller configuration
Issue 5: Using Linear Mode Incorrectly
Correct linear scaling setup:
Raw Input (mA) Scaled Output (°F)
4.0 32.0 (freezing)
12.0 72.0 (midpoint)
20.0 112.0 (max)
Configuration:
- Raw Min: 4
- Raw Max: 20
- Scaled Min: 32
- Scaled Max: 112
Verification Procedure
Step 1: Measure Actual Current
- Disconnect signal wire at controller
- Place ammeter in series
- Read actual current (should be 4-20mA range)
Step 2: Compare to Displayed Value
- Calculate expected value based on current and scaling
- Compare to controller display
- If mismatch, reconfigure scaling
Step 3: Signal Simulation
- Use 4-20mA signal generator (or calibrator)
- Apply known current values: 4mA, 12mA, 20mA
- Verify controller reads expected engineering values
Wiring Best Practices
For reliable 4-20mA signals:
- Use shielded twisted pair cable
- Ground shield at one end only (controller end)
- Keep signal wiring away from power cables
- Maximum recommended distance: 1000ft (300m) for typical gauges
Troubleshooting Summary
| Symptom | Likely Cause | Check |
|---|
| Reads zero | Wrong input type | Hardware switch, software config |
| Erratic | Wiring/noise | Shield grounding, cable routing |
| Stuck min | Open circuit | Wiring continuity |
| Stuck max | Short circuit | Wiring for shorts |
| Wrong value | Scaling mismatch | Sensor range vs config |