Software Version: Niagara N4
Error Code: WARNING [binder] unresolved: slot:/points/[point_name]
Go to every px file, go to edit mode, and check the ords (click on the Replace in ords button under the Bound Ords window on the top right). This error typically occurs when graphics reference points that no longer exist or have been moved. Check for tabbed panes or graphics that reference non-existent points and remove them.