This guide covers best practices for reusing existing Siemens control panel enclosures when migrating to Honeywell building automation systems.
| Benefit | Details |
|---|---|
| Cost savings | Avoid new enclosure purchase ($200-800+) |
| Time savings | No new tub installation required |
| Built-in features | Existing receptacle, power supply, terminal blocks |
| Reduced disruption | Less demolition work |
| Established location | Conduit routes already in place |
Before committing to reuse, verify:
| Siemens Component | Check Against Honeywell |
|---|---|
| Backpan depth | Controller mounting depth |
| Width/height | Component spacing requirements |
| DIN rail positions | Honeywell DIN rail components |
| Knockout locations | New conduit entries if needed |
| Model Series | Typical Dimensions | Suitable For |
|---|---|---|
| Talon | 20" x 16" x 6" | Small Spyder systems |
| APOGEE MEC | 24" x 24" x 8" | Medium systems |
| APOGEE MBC | 30" x 24" x 8" | Larger systems |
| Controller | Dimensions | Notes |
|---|---|---|
| Spyder | ~6" x 4" x 2" | Multiple per enclosure |
| Excel Web | ~12" x 8" x 3" | Controller + expansion |
| WEBs-N4 | Variable | Depends on JACE model |
Evaluate power supply:
Plan component layout:
Install new DIN rails if positions don't match
Siemens terminal blocks can often be reused if:
| Siemens Typical | Honeywell Equivalent |
|---|---|
| AI terminals | AI inputs on Spyder |
| AO terminals | AO outputs on Spyder |
| DI terminals | DI inputs on Spyder |
| DO terminals | DO outputs on Spyder |
| Comm (Lon/P1) | BACnet MS/TP or IP |
Note: Maintain clear separation between low-voltage signal wiring and line voltage.
| Model | Output | Compatible with Honeywell? |
|---|---|---|
| 24VAC 40VA | 24VAC | Yes, for small loads |
| 24VAC 75VA | 24VAC | Yes, typical Spyder system |
| 24VAC 100VA+ | 24VAC | Yes, larger systems |
| 24VDC | 24VDC | Only for DC-powered devices |
Calculate total Honeywell system load:
If existing supply < calculated load, replace.
Solution: Use smaller form factor controllers or add adjacent enclosure
Solution: Install adapter brackets or new backpan
Solution: Replace with appropriately sized 24VAC transformer
Solution: Replace with new GFCI receptacle if required by code
After migration, update:
Verify installation meets: