All About Metasys Interlocks - Complete Tutorial
Interlocks in Metasys provide safety and coordination between equipment, ensuring proper sequencing and protection against unsafe operating conditions.
What Are Interlocks?
Interlocks are logical connections between equipment that:
- Prevent unsafe operation
- Coordinate equipment sequencing
- Protect mechanical systems
- Enforce operational dependencies
Types of Interlocks
Safety Interlocks
Protect equipment and personnel:
| Interlock | Purpose |
|---|
| Freeze protection | Stops fan if coil temp drops too low |
| Fire/smoke | Shuts down AHU on fire alarm |
| High static | Limits fan speed on high duct pressure |
| Motor overload | Disables equipment on electrical fault |
Operational Interlocks
Ensure proper sequence of operations:
| Interlock | Purpose |
|---|
| Chiller flow proof | Requires pump flow before starting chiller |
| AHU enable | Requires OA damper open before fan start |
| Exhaust/supply coordination | Balance supply and exhaust fans |
| Lead/lag | Coordinate multiple equipment staging |
Configuring Interlocks in Metasys
Using CCT (Controller Configuration Tool)
- Open equipment module in CCT
- Navigate to Interlocks section
- Define input source (the triggering condition)
- Set action (what happens when triggered)
- Configure delay timers if needed
- Download to controller
Common Interlock Parameters
| Parameter | Description |
|---|
| Source Point | The monitored condition |
| Condition | Equal, Not Equal, Greater Than, etc. |
| Action | Disable, Enable, Shutdown, etc. |
| On Delay | Time before interlock activates |
| Off Delay | Time before interlock releases |
| Priority | Override level (higher = stronger) |
Interlock Logic Examples
AHU Freeze Protection
IF Coil_Temp < 38°F
AND Condition persists > 30 seconds
THEN:
- Close OA damper to minimum
- Open heating valve to 100%
- If temp continues dropping, stop supply fan
Chiller Safety Interlock
IF Chilled_Water_Flow < Minimum_Flow
AND Chiller is RUNNING
THEN:
- Alarm: Low flow condition
- After 60 seconds: Stop compressor
- Lock out until flow proven
VAV Minimum Airflow
IF Occupancy = UNOCCUPIED
THEN:
- Reduce minimum airflow to 0 CFM
ELSE:
- Maintain ventilation minimum per ASHRAE 62.1
Testing Interlocks
Pre-Commissioning Checklist
- Verify point connections - Ensure all interlock inputs are wired correctly
- Simulate conditions - Force input values to test logic
- Check timing - Verify delays operate as designed
- Document results - Record all test conditions and responses
Safe Testing Procedures
- Test during unoccupied periods when possible
- Have manual overrides ready
- Coordinate with operations staff
- Start with less critical interlocks first
- Never bypass safety interlocks without proper lockout
Troubleshooting Interlocks
Equipment Won't Start
- Check for active interlocks in point status
- Review interlock conditions in CCT
- Verify input point values
- Check for latched fault conditions
- Look for priority command overrides
Interlock Keeps Tripping
- Verify sensor calibration
- Check for intermittent wiring issues
- Review setpoints (may be too sensitive)
- Examine timing parameters
- Look for environmental causes
Best Practices
Design
- Document all interlock logic in sequence of operations
- Use consistent naming conventions
- Include appropriate time delays to prevent nuisance trips
- Consider failure modes (what if sensor fails?)
Implementation
- Test each interlock individually during commissioning
- Verify all hardwired safety interlocks first
- Train operators on interlock behavior
- Provide clear alarm messages
Maintenance
- Periodically test critical safety interlocks
- Document any changes to interlock logic
- Review interlock performance after system modifications
Video Tutorial
For a complete visual demonstration of Metasys interlock configuration:
Video Tutorial: